Reset Volume Controller: 3800 Series, Direct/Reverse Acting, Normally Open or Normally Closed

  • Sale
  • $395.00


Reset Volume Controller: 3800 Series, Direct/Reverse Acting, Normally Open or Normally Closed

Item 20RG02
Mfr. Model P-3800-1

Reset volume controls connect to a pneumatic thermostat or other pneumatic device and control the airflow through a VAV (variable air volume) box. They act as sub-controllers for the thermostat and interpret the pneumatic signal to optimize airflow for their HVAC branch.

Brand   JOHNSON CONTROLS
Series   3800
Manufacturer Part Number  P-3800-1
Controller Action Direct  /  Reverse Acting
Damper ActionNormally Open or Normally Closed
Thermostat Required for HeatingDirect/Reverse Acting
Thermostat Required for CoolingDirect/Reverse Acting
Minimum Setpoint Range0 to 1.6 in wg
Maximum Setpoint Range0.15 to 3.2 in wg
Reset Start Point Factory Setting8 psi
Reset Start Point Range3 to 10 psi
Air Consumption @ 20 psi25 scim
Maximum Signal Pressure10 psig
Output Sensitivity2.25 psi / 0.01 in wc
Output Pressure Capability20 psig to Supply Pressure
Minimum Operating Temperature60 °F
Maximum Operating Temperature85 °F
Mounting OrientationHorizontal; Vertical
Air Inlet Type Barb
Air Inlet Size  3/8 in
Housing Color  Black
Housing Material  Noryl
Application  Cooling; Heating
Weight  1 lb
Includes  Mounting Bracket
Standards RoHS Compliant
UNSPSC31251504
Country of Origin Mexico